Tools >> 3M Water Leak Detector
3M Water Leak Detector Sensor must be installed by professional electricians.
Do not install the detector in the place: where the detector is watered, high temp & hi humidity, where temp change is sharp, where vibration or electric noise is intense. We do not carry Omron
3M Water Leak Detector
![]() |
3M Water Leak Detector WR-TW-KO1000 (Analog Signal) 3M ID 7000009194 UPC 04710367047698
1. Status Indicator Light: Green ( power on ) , Red ( Leak Detection) 2. Adjustable Sensitivity Level 3. Can detect pure water and Photoresist (when using S-1F or B-3P) 4. Power Source: AC110V or 220V 5. Only runs under AC 19V on the detecting sensor cable. 6. Two control outputs (2C output) 7. After detected Water Leak. Adjust Sensor Gain to Low to reset. 8. CE approved.
* Please keep the Sensor Cable & extension wire length under 100 meter. Please check with us for more info. * Need to be installed on the PF113N base socket.
Sensor Cable: S-1F(recommended) / B-3P(recommended) / S-1FP / PS-1R Cable Holder Adhesive Mount: SS-1, SS-5, SS-6 Model Number: WL-TW-KO1000 |
![]() |
3M Water Leak Detector WL-AD-2002-A 漏水檢知器終極數位型 (Digital Signal) 1. LED Indicator Light on panel ‧ Green (Power) ‧ Red (Water) ‧ Red (Sensor Short) ‧ Yellow (Sensor Open) 2. Adjustable Sensitivity Level Setting 3. Detectable of Ultra-pure Water and some Photoresist (when using S-1F or B-3P) 4. Triple Power Voltage Options: AC 100~110V or AC 200~220V 5. Reset Button (by 1-2 degree), upon water leakage detected 6. Dual Output Signal Indicator: Sensor Open; and Sensor Short/Water Leakage 7. Water Leaking Alarm/Reset Time range: 2 sec / 2 sec 8. Circuit Breaking Alarm Time: 2 sec 9. Once broken detection circuit is reconnected, detection will automatically resume ‧ Sensor and extension wire shall keep within 350m (keep away from sources of interference, such as UPS, motors and high-voltage cables, by at least 20cm) ‧ Complies with 11-hole adaptor, model PF113N ‧ Sensor is to be connected with 3M special kits so as to detect any disconnect of the sensor
Only runs under DC pulse 9V on the detecting sensor cable. Two control outputs (1C output - no voltage) CE approved.
Sensor Cable: S-1F(recommended) / B-3P(recommended) / S-1FP / PS-1R Cable Holder Adhesive Mount: SS-1, SS-5, SS-6 Model Number: WL-AD-2002-A Current of
sensor shortage: < 1mA |
![]() |
3M Water Leak Detector WL-AD-2002-B 漏水檢知器精準數位型 (Digital Signal) 1. LED Indicator Light on panel ‧ Green (Power) ‧ Red (Water) ‧ Red (Sensor Short) 2. Adjustable Sensitivity Level Setting 3. Detectable of Ultra-pure Water and some Photoresist (when using S-1F or B-3P) 4. Triple Power Voltage Options: AC 100~110V or AC 200~220V 5. Reset Button (by 1-2 degree), upon water leakage detected 6. Dual Output Signal Indicator: Sensor Short/Water Leakage 7. Water Leaking Alarm/Reset Time range: 2 sec / 2 sec 8. Circuit Breaking Alarm Time: 2 sec 9. Once broken detection circuit is reconnected, detection will automatically resume ‧ Sensor and extension wire shall keep within 350m (keep away from sources of interference, such as UPS, motors and high-voltage cables, by at least 20cm) ‧ Complies with 11-hole adaptor, model PF113N ‧ Sensor is to be connected with 3M special kits so as to detect any disconnect of the sensor
Only runs under DC pulse 9V on the detecting sensor cable. Two control outputs (1C output - no voltage) CE approved.
Sensor Cable: S-1F(recommended) / B-3P(recommended) / S-1FP / PS-1R Cable Holder Adhesive Mount: SS-1, SS-5, SS-6 Model Number: WL-AD-2002-B
|
|
3M Water Leak Detector WL-AD-2002-C 漏水檢知器全能數位型(Digital Signal) 1. Status Indicator Light: Green ( power on ) , Red ( Leak Detection) 2. Adjustable Sensitivity Level 3. Detectable of Ultra-pure Water, IPA and low conductive liquid. 4. Power Source: AC110V or 220V 5. Only runs under DC pulse +5V/ - 9V on the detecting sensor cable. 6. One control outputs (1C output) 7. After detected Water Leak. Adjust Sensor Gain back to 1~2 scale to reset. 8. CE approved. 9. Water Leak Detecting time:3 Sec / Reset time: 3 Sec.
‧ Sensor and extension wire shall keep within 350m (keep away from sources of interference, such as UPS, motors and high-voltage cables, by at least 20cm) ‧ Complies with 11-hole adaptor, model PF113N
Sensor Cable: B-3P(recommended) Cable Holder Adhesive Mount: SS-1 Model Number: WL-AD-2002-C
|
![]() |
3M Water Leak Detector WR-NA 漏水檢知器蜂鳴型 (Analog Signal) AMAT P/N 0820-01009 For Indoor Use ( Do not install in the area directly expose to water, extremely humid, or close to electronic device with strong radio wave) Model Number: WR-NA
Warning: Light & Buzzer - Visual and audible alarms
After detected Water Leak. Adjust Sensor Gain back to 2~3 scale to reset. Please keep the Sensor Cable & extension wire length under 150 meter Termination kit TR-820 Features
● Leak water sensor used for leak detector with disconnection alarm
function. ● Not for PS-1R sensor.
|
![]() |
3M 漏液檢知器LLD 24014系列 3M Water Leak Detector LLD 24014-A LLD 24014-B LLD 24014-A
LLD 24014-B
If you have question for this product, please contact us for more info.
|
|
|
※ 3M Water Leak Detector need PF113N base mount relay socket.(11-hole adaptor) ※ 3M 漏水檢知器需搭配PF113N型11孔插座 |
Sensor Cable 漏水センサー
Choice of Sensor Cable
S-1F Very sensitive and apply to clean and dry area.
B-3P Less sensitive and apply to dusty or humid area.
![]() |
![]() |
B-3P B-3P Memo 100 M/RL 3M ID 7100195398
* Clear Plastic Vinyl Chloride Sealed/UL OK/ VW-1 Flame Retardant * Stainless Wire SUS 304 ψ0.3mm (12 strands) * Operation Temp: -15℃~50℃ * RH: under 90% * Can be use in humid or dusty area. * Cable Holder Adhesive Mount: SS-1、SS-5
Apply to wide area / dusty / humid/
|
![]() |
![]() |
S-1F 3M SUMITOMO S-1F 注意事項 AMAT P/N : 1270-01392 100 M/RL. 3M ID 7000007346; UPC 04901690071737
* Clear Plastic Vinyl Chloride Sealed/UL OK/ VW-1 Flame Retardant * Stainless Wire SUS 304 ψ0.3mmx1.5mm * Operation Temp: -15℃~50℃ * RH: under 90% * Not for humid or dusty area. * Cable Holder Adhesive Mount: SS-6
Not suitable for dusty or high humidity area.
|
![]() |
![]() |
S-1FP * Clear Plastic Sealed/UL OK/ VW-1 Flame Retardant * Stainless Wire SUS 304 ψ0.3mmx1.5mm * Operation Temp: -15℃~50℃ * RH: under 90% * Easy to spiral along the pipes. * For clean surface. * Cable Holder Adhesive Mount: SS-1
For piping area. Please use cable tie to secure the S-1FP sensor cable to the pipes.
|
![]() |
|
PS-1R PS-1R 注意事項 3M ID 7000007730
* Wire lenght: 1.5M * Operation Temp: -15℃~50℃ * RH: under 95% * 70g * Cable Holder Adhesive Mount: SS-1
PS-1R with a built-in 820kΩ resistor, it is compatible with the water leakage detector ( WR-NA, 2002A) with self-diagnosis sensor open warning function. PS-1R memo When connecting multiple PS-1R sensors in parallel to the detector, please do not use more than 3 pcs. |
Sensor Cable Holder Adhesive Mount Sticker with double-sided tape to secure the sensor
![]() |
SS-1 Sensor Cable Holder Adhesive Mount 貼片 Sticker Stainless Mount with Acrylic adhesive for flat and clean surface area.
規格: |
|
![]() |
SS-5 Sensor
Cable Holder Adhesive Mount 貼片 Sticker Plastic case with Acrylic adhesive - for floor, tile 規格: |
|
![]() |
SS-6 Sensor
Cable Holder Adhesive Mount 貼片 Sticker ABC Plastic with 3M double sided adhesive - for flat & clean surface.
規格: |
![]() |
* Please do install & secure the sensor cable properly. * Certain area need to apply specific glue in order to secure the cable. Please contact us. (注意)
|
Instruction for installing 3M KO1000
3MWater Leak Detector/ Water Leak Detector Sensor (pdf 3.6mb)